Al Conductor HEPR/PO 0.6/1kV LSOH Power Cable 90℃
Application
These cables are designed for main power lines of permanent routing in wind tower installation.
Standards
IEC 60502
Construction
Conductor:Aluminium conductor, class 2 to IEC 60228.
Insulation: HEPR. XLPE can be offered upon request.
Inner Covering: rubber compound type GM1b.
Sheath:Compound based on polyolefin, type HXM1.
Technical Data
Rated Voltage Uo/U (Um):0.6/1kV
Operating Temperatures:-40℃~+ 90℃
Minimum Bending Radius:4×OD
Short-circuit Temperature:250℃
Flame Retardant:IEC 60332-1
Halogen Free:IEC 60754
Gases Corrosively:DIN EN 50267-2/ IEC 60754
Smoke Density:IEC 61034
Oil Resistant:Yes
Ozone Resistant:Yes
UV Resistant:Yes
Dimensions and Weight
Construction | Nominal Overall Diameter | Nominal Weight |
---|---|---|
No. of cores×mm² | mm | kg/km |
1×50 | 13.0 | 266 |
1×70 | 15.0 | 352 |
1×95 | 16.5 | 450 |
1×120 | 18.0 | 556 |
1×150 | 20.0 | 686 |
1×185 | 22.5 | 842 |
1×240 | 26.0 | 1076 |
1×300 | 29.0 | 1299 |
1×400 | 32.5 | 1680 |
3×150 | 44.0 | 2756 |
4×150 | 49.0 | 3367 |